Gas Burner Adjustment
Midbrook does not recommend setting or adjusting the gas burner unless the operator has been trained by a certified gas burner service technician.
That said, gas burners are set up by measuring the amount of oxygen that is left at the end of the tube by inserting a meter at the exhaust stack.
At the pilot setting that oxygen ratio mix should read 12% - 16%. For the burner to fire consistently, there should not be more oxygen used than that percentage.
- In order to regulate the gas air mixture the operator should find the small pilot line’s shut off/adjusting valve.
- Open this line for more gas and close for less gas.
- Turn the main gas valve off and the unit will stay on the pilot setting during this final adjustment.
- Start and stop the unit at least 5 times to make sure the system fires correctly.
The proportionating valve and main gas regulator control low fire.
- By turning the top-adjusting stem out or up, it will reduce the output.
- The setting should be at 16% oxygen on low fire.
- Once the fluid has reached temperature the gas trane should cycle down to this low fire setting.
- If the trane goes to low fire and temperature of the water continues to climb, then you should check the pilot setting again or the proportionating valve setting.
High fire
- When unit is on high fire the oxygen reading should be 4%
- Control is by the main regulator and the dung valve
- If the reading is too low, then close down the dung valve until the 4% ratio is reached
- Normally there is no need to adjust for air flow.